TC200/300 Intelligent Digital Explosion-Proof Thermostat

TC200/300 (40 A, 220 V) is an on-site intelligent thermostat that delivers accurate and reliable temperature control for heat tracing systems. It supports local installation, display and control, and enables remote monitoring. This intelligent temperature controller can monitor temperature, current and voltage and is equipped with a full set of alarm functions.

  • Overview
  • Recommended Products

Function Introduction

Built-in sensor for temperature measurement and real-time display

Supports RS485 Modbus RTU communication

Displays real-time loop temperature and control differential value; activates heat tracing cables when temperature drops below set value, and deactivates them when temperature rises above set value

Equipped with viewing window and external operation buttons

Parameters can be set and modified in real time

Displays real-time loop voltage and current

Suitable for local control of self-limiting heating cables, constant-power heating cables and mineral insulated MI heating cables

Supports sensor fault detection

The circuit cuts off when temperature exceeds set value and resumes operation when temperature falls below set value

Relay output

Pulse start function to reduce inrush current

 

Technical Data

Model: TC200/300

Ambient Temperature Range: -40℃—+55℃

Relative Humidity: ≤95%

Housing Material: Carbon Steel / 304 Stainless Steel / 316 Stainless Steel

Dimension(LWH mm): 200×200×130

Ingress Protection: IP66

Rated Current: 16 A, 25 A, 32 A, 40 A

Rated Voltage: AC 220 V (±10%)

Sensor Type: 3-wire PT100

Measurement Accuracy: ±0.5℃

Communication: RS485 Modbus RTU

Temperature Control Range: -100℃~300℃

Cable Entry Specification: 3×M25+2×M20

 

Alarm Functions

High temperature alarm, low temperature alarm, overvoltage alarm, undervoltage alarm, overcurrent alarm, undercurrent alarm, differential value setting.

Temperature alarm: The device triggers an alarm when the temperature exceeds the preset upper limit or falls below the preset lower limit.

Voltage alarm: The device triggers an alarm when the voltage exceeds the preset maximum value or falls below the preset minimum value.

Current alarm: The device triggers an alarm when the current exceeds the preset maximum value or falls below the preset minimum value.

Differential setting function: Adjustable differential values for temperature alarm, voltage alarm, current alarm and setpoint hysteresis.

 

Applicable Hazardous Areas

Gas explosion protection (Ex db IIC T6 Gb): Suitable for Zone 1 / Zone 2. Applicable for highly dangerous gases (such as hydrogen, acetylene) with low surface temperature class T6.

Dust explosion protection (Ex tb IIIC T80°C Db): Suitable for Zone 21 / Zone 22, designed for conductive dust, surface temperature limit 80°C.

Comprehensive application: The equipment can be used in environments with mixed gas and dust hazards, such as petroleum, chemical and pharmaceutical industries.